Publication 1757-IN510A-EN-P - October 2003
Supplementary Procedures 8-27
27. Click the CPM icon and click Edit
⇒ Delete.
28. Click Delete Selected object(s) to delete the CPM and its
associated CEE.
29. Close Control Builder.
Installing and connecting Redundant Chassis Pair (RCP)
Hardware
Refer to the following data in Knowledge Builder for general
information about Controller redundancy and how to install and
connect the 1757-PLX52, 1757-SRM Redundancy Module (SRM), and
1756-CNBR redundant ControlNet Bridge module (CNB).
• Navigate in Knowledge Builder to Control Builder Components
Theory
⇒
Controller Redundancy Functionality before
upgrading to a Redundant Chassis Pair for general information
about Controller redundancy and related terminology.
• Navigate in Knowledge Builder to Control Hardware
Installation Guide
⇒
Controller Module Installation and
Removal for information on installing the 1757-PLX52 module.
• Navigate in Knowledge Builder to Control Hardware
Installation Guide
⇒
Redundancy Module Installation and
Removal for information on installing the 1757-SRM module.
• Navigate in Knowledge Builder to Control Hardware
Installation Guide
⇒
ControlNet Communication Module
Installation and Removal for information on installing the
1756-CNB module.
Updating Firmware Revision Levels
Refer to Upgrading Hardware Component Firmware on page 7-4 to
check/upgrade 1757-PLX52, 1756-CNB, and 1757-SRM firmware.
IMPORTANT
Stop! It is essential that you check the firmware
revision levels for
ALL ProcessLogix hardware
components after a ProcessLogix software
installation.
Do
not proceed until you have upgr aded the
firmware.