Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 327

Publication 1758-UM002D-EN-P - October 2010
Enron Modbus Protocol for the 1758-FLO DataSite Controller 327
General input configuration variables
Register
Description
Access
3053
Input unit type.
Bit 3: 0 = US, 1 = Metric
R/W
3054
Flow calculation type.
0 = AGA-3 (1992), 1 = AGA-7
R/W
3055
Compressibility calculation type
0 = Gas analysis, 1 = HR-GR-COR, 2 = GR-CO2-N2
R/W
3056
Static pressure tap location
0 = upstream, 1 = downstream
R/W
3057
Pressure type
0 = gauge, 1 = absolute
R/W
3058
Time duration for low flow pulse limit check (in seconds).
Range: 0…5 s (AGA-7 only)
R/W
3059
Calculation interval
R/W
Instantaneous input register address
Register
Description
Access
3060
Temperature input register Modbus address
R/W
3061
Static pressure input register Modbus address
R/W
3062
Differential pressure input register Modbus address
R/W
AGA-3 configuration variables
Register
Description
Access
3063
Orifice material
0 = stainless, 1 = monel, 2 = carbon steel
R/W
3064
Tube material
0 = stainless, 1 = monel, 2 = carbon steel
R/W
Instantaneous input register data type
Register
Description
Access
3065
DP register data type
0 = ushort, 1 = float
R/W
3066
P register data type
0 = ushort, 1 = float
R/W
3067
T register data type
0 = ushort, 1 = float
R/W