Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 298

Publication 1758-UM002D-EN-P - October 2010
298 Extension Modbus Protocol for DataSite Controllers (1758-FLO)
There is no event code for command number 16.
Command Number 17: Set Up the Calculation Input Parameters
Use command number 17 to set up the corresponding parameters, excluding
the gas component parameters, for one meter run.
Return codes for command number 16
Return Code
Description
00
OK
01
Meter run is invalid
100
Pass code is incorrect
Other
Invalid
Parameters for command number 17
Address
Data Type
Attribute
Description
49025
u_short
RW
17
49026
u_short
R
Return code
49027
u_short
W
Meter run (0…7)
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved
49035
u_short
W
Whether the meter run is enabled
0: Disable
1: Enable
49036
u_short
W
Type of measurement units
0: U.S.
1: Metric
49037
u_short
W
Accumulate
0: Do not accumulate
1: Accumulate
49038
u_short
W
Use automatic components
analysis instrument
0: Disable
1: Enable
49039
u_short
W
Calculation type
0: AGA3
1: AGA7
49040
u_short
W
Algorithm for the calculation of
the compressibility factor
0: Gas Analysis
1: HV-GR-CO2
2: GR-CO2-N2
49041
u_short
W
Run interval