Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 286

Publication 1758-UM002D-EN-P - October 2010
286 Extension Modbus Protocol for DataSite Controllers (1758-FLO)
There is no event code for command number 4.
Command Number 5: Disable/Enable the Flow Calculation
Use command number 5 to enable or disable the flow calculation for a meter
run.
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved
49035
u_short
R
Device name 1
49036
u_short
R
Device name 2
49037
u_short
R
Device name 3
49038
u_short
R
Device name 4
49039
u_short
R
Device name 5
49040
u_short
R
Device name 6
49041
u_short
R
Device name 7
49042
u_short
R
Device name 8
Return codes for command number 4
Return Code
Description
00
OK
100
Pass code is incorrect
Other
Invalid
Parameters for command number 5
Address
Data Type
Attribute
Description
49025
u_short
RW
5
49026
u_short
R
Return code
49027
u_short
W
Meter run (0…7)
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved
49035
u_short
W
0: Disable
1: Enable
Parameters for command number 4 (Continued)
Address
Data Type
Attribute
Description