318 Extension Modbus Protocol for DataSite Controllers (1758-FLO)
There is no event code for command number 27.
Command Number 28: Disable/Enable the Automatic Components
Analysis Instrument
Use command number 28 to set whether or not to read the gas component
parameters from a gas component analyzer automatically.
There is no event code for command number 28.
Return codes for command number 5
Return Code
Description
00
OK
100
Pass code is incorrect
Other
Invalid
Parameters for command number 28
Address
Data Type
Attribute
Description
49025
u_short
RW
28
49026
u_short
R
Return code
49027
u_short
W
Meter run (0…7)
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved
49035
u_short
W
Get gas component parameters
from the gas component analyzer.
0: Disable
1: Enable
Return codes for command number 28
Return Code
Description
00
OK
01
Meter run is invalid
02
Automatic components analysis instrument selection is invalid
100
Pass code is incorrect
Other
Invalid