SDNP3 Data Objects
This table lists the types of SDNP3 data objects and their descriptions.
SDNP3 Data Objects and Their Descriptions
SDNP3 Data Object
Object
Number
Description
Binary input object
1
Current status of the binary input, digital input (DI) data
Binary input change object
2
Binary input changes and new values, DI data
Binary output object
10
Current value of the binary output, digital output (DO) data
Binary counter object
20
Current data of counter input, counter input (PI) data
Binary freeze counter object
21
Current data of freeze counter input, freeze counter input (Freeze PI) data
Binary counter change object
22
Counter input changes and new values (PI) data
Binary freeze counter change object
23
Freeze counter input changes and new values (Freeze PI) data
Analog input object
30
Current data of analog input, analog input (AI) data
Analog input change object
32
Analog input changes and new values, AI data
Analog output object
40
Current value of the analog output, analog output (AO) data
Time and date object
50
Current time of the DataSite controller
Class object
60
Event class 0, 1, 2, 3
Internal indication (IIN) sign object
80
Indicates current communication, data, and operation status of the DataSite
controller
String object
110
String object data
String change object