DataSite DNP3 Configuration Utility (DS DNP3) 253
Configure a DS DNP3 session
The DataSite controller allows up to four sessions to be executed
simultaneously. This means, when there is a slave station with multiple master
stations, the slave station can connect up to four master stations.
Follow these steps to configure a DNP3 session.
1.
Select the session you want to configure from the navigation pane.
The settings dialog box for the selected session appears.
2.
In the Station box, enter the number of the master station.
This is the communication address of the host computer.
TIP
65533 and 65534 are addresses used for broadcast.
65535 is reserved by the system. These three
addresses cannot be used for session stations.