274 Extension Modbus Protocol for DataSite Controllers (1758-FLO)
Modbus Registers for Flow Configuration Parameters (RO)
Modbus addresses for flow configuration parameters
Meter Run
Starting Address
Parameter
Address
Address Number
0
32101
X
100
1
32201
X + 100
100
2
32301
X + 200
100
3
32401
X + 300
100
4
32501
X + 400
100
5
32601
X + 500
100
6
32701
X + 600
100
7
32801
X + 700
100
Flow configuration parameters
Parameter Name
Description
Data Type
Modbus Address
of Meter Run 0 = X
Enable
Bit 0: Enable calculation
Bit 1: Enable accumulation
Bit 2: Parameter modification flag
Bit 3: Type of measurement unit. 0: imperial, 1: metric
Bit 4: Flag for usage of the automatic component analysis
instrument
u_short
32101
CalInterval
Calculation interval
u_short
32102
piInterval
BMP (base multiplier period)
u_short
32103
dp_DPoint
Data point configuration (differential pressure address or pulse)
u_short
32104
p_DPoint
Data point configuration (static pressure address)
u_short
32105
t_DPoint
Data point configuration (temperature address)
u_short
32106
usAGA_Type
AGA calculation method.
0: AGA3, 1: AGA7
u_short
32107
usTapLocation
Tap location
0: Upstream, 1: Downstream
u_short
32108
usPressType
Pressure type
0: Gauge, 1: Absolute
u_short
32109
usZ_mode
AGA8 methods
0: Gas analysis, 1: HV-GR-CO2, 2: GR-CO2-N2
u_short
32110
usOrifice_Type
Orifice material
0: Type 304 and 316 stainless steel, 1: Monel, 2: Carbon steel
u_short
32111
usPipe_Type
Tube material
0: Type 304 and 316 stainless steel, 1: Monel, 2: Carbon steel
u_short
32112
usGr_Type
AGA8 relative density condition type
0: Real, 1: Ideal
u_short
32113