Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 297
![background image](/manuals/579221/297/background.png)
Publication 1758-UM002D-EN-P - October 2010
Extension Modbus Protocol for DataSite Controllers (1758-FLO) 297
Command Number 16: Read the Alarm Range of Input Parameters
Use command number 16 to read the upper and lower alarm limits and alarm
dead-band of static pressure, temperature, and differential pressure or pulse.
Parameters for command number 16
Address
Data Type
Attribute
Description
49025
u_short
RW
16
49026
u_short
R
Return code
49027
u_short
W
Meter run (0…7)
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved
49035
u_short
R
Whether the alarm for differential
pressure or pulse is enabled
0: Disable
1: Enable
49036
float
R
Upper alarm limit of differential
pressure or pulse
49038
float
R
Lower alarm limit of differential
pressure or pulse
49040
float
R
Alarm dead-band of differential
pressure or pulse
49042
u_short
R
Whether the alarm for static
pressure is enabled
0: Disable
1: Enable
49043
float
R
Upper alarm limit of static
pressure
49045
float
R
Lower alarm limit of static
pressure
49047
float
R
Alarm dead-band of static
pressure
49049
u_short
R
Whether the alarm for
temperature is enabled
0: Disable
1: Enable
49050
float
R
Upper alarm limit of temperature
49052
float
R
Lower alarm limit of temperature
49054
float
R
Alarm dead-band of temperature