Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 291

Publication 1758-UM002D-EN-P - October 2010
Extension Modbus Protocol for DataSite Controllers (1758-FLO) 291
There is no event code for command number 10.
Command Number 11: Disable/Enable the Accumulation
Calculation
Use command number 11 to disable or enable accumulation calculation for a
meter run.
1
Return codes for command number 10
Return Code
Description
00
OK
01
Meter run is invalid
100
Pass code is wrong
Other
Invalid
Parameters for command number 11
Address
Data Type
Attribute
Description
49025
u_short
RW
11
49026
u_short
R
Return code
49027
u_short
W
Meter run (0…7)
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved
49035
u_short
W
Whether accumulation calculation
is enabled.
Event codes for command number 11
Event Name
Event Code
EVENT_START_ACCUMULATE
14
EVENT_STOP_ACCUMULATE
15
Return codes for command number 11
Return Code
Description
00
OK
01
Meter run is invalid
02
The value for accumulation input is invalid
100
Pass code is incorrect
Other
Invalid