Rebuild the aga files, Delete the datasite workbench program, Clear the dnp3 parameters – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 193

Publication 1758-UM002D-EN-P - October 2010
DataSite Flow Configuration Utility (DS FloConfig) 193
Rebuild the AGA Files
Follow these steps to clear all the history and event records.
1.
Set the controller into the Service mode.
2.
Select the AGA File Initialization check box.
3.
Click Set.
All the history and event records are cleared.
4.
Click Run, and exit the service mode.
Delete the DataSite Workbench Program
Follow these steps to delete the DataSite Workbench program that is on the
DataSite controller.
1.
Set the controller into the Service mode.
2.
Select the DS Workbench Initialization check box.
3.
Click Set.
The DataSite Workbench program is deleted from the DataSite
controller.
4.
Click Run, and exit the service mode.
Clear the DNP3 Parameters
Follow these steps to clear the values of the DNP3 parameters.
1.
Set the controller into the Service mode.
2.
Select the DNP3 Initialization check box.
3.
Click Set.
The DNP3 parameter settings are deleted from the DataSite controller.
4.
Click Run, and exit the service mode.