Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 216

Publication 1758-UM002D-EN-P - October 2010
216 DataSite Flow Configuration Utility (DS FloConfig)
HART state register
+0 = state 0
+1 = state 1
Command
35
Purpose
Write Primary Variable Range Values
Send register
+0 = Primary Variable 0 code, 8-bit unsigned integer
+1, 2 = Primary Variable upper range value (float point)
+3, 4 = Primary Variable lower range value (float point)
Return register
Not used
Unit register
Not used
HART state register
+0 = state 0
+1 = state 1
Command
38
Purpose
Reset Configuration Changed Flag
Send register
Not used
Return register
Not used
Unit register
Not used
HART state register
+0 = state 0
+1 = state 1
Command
40
Purpose
Enter/Exit Fixed Primary Variable Current Mode
Send register
+0, 1 = Actual fixed Primary Variable current level, units of
milliamperes (float point)
Return register
Not used
Unit register
Not used
HART state register
+0 = state 0
+1 = state 1
Command
44
Purpose
Write Primary Variable Units
Send register
+0 = Primary Variable units code, 8-bit unsigned integer
Return register
Not used
Unit register
Not used
HART state register
+0 = state 0
+1 = state 1
Command
48
Purpose
Read Additional Transmitter Status
Send register
Not used
Description of HART commands (Continued)