Command number 13: set the input parameters – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 292
Publication 1758-UM002D-EN-P - October 2010
292 Extension Modbus Protocol for DataSite Controllers (1758-FLO)
Command Number 12: Read Disable/Enable Setting for
Accumulation Calculation
Use command number 12 to read the disable/enable setting for accumulation
calculation for a meter run.
There is no event code for command number 12.
Command Number 13: Set the Input Parameters
Use command number 13 to set up parameters for pressure, temperature and
differential pressure or pulse. These parameters include the data address, type,
and factors K and B.
Parameters for command number 12
Address
Data Type
Attribute
Description
49025
u_short
RW
12
49026
u_short
R
Return code
49027
u_short
R
Meter run (0…7)
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved
49035
u_short
R
Whether or not the accumulation
calculation is enabled on this
meter run.
Return codes for command number 12
Return Code
Description
00
OK
01
Meter run is invalid
100
Pass code is incorrect
Other
Invalid
Parameters for command number 13
Address
Data Type
Attribute
Description
49025
u_short
RW
13
49026
u_short
R
Return code
49027
u_short
W
Meter run (0…7)
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved