DataSite Flow Configuration Utility (DS FloConfig) 225
5.
In the Scan Time box, enter the number of units and select the time unit
to specify the time cycle of scanning HART equipment data.
For example, if you enter "1" for the number of units, and select
"500 ms" for the time unit, the scan time will be 1 x 500 ms = 500 ms.
This means that the current HART scan block will be executed every
500 ms.
6.
In the Send Register box, define the register for storing command data.
7.
In the Return Register box, define the register for storing command
response data.
8.
In the Unit Register box, define the register for storing the unit of
HART equipment data returned.
9.
In the State Register box, define the register for storing the HART
equipment state returned.
10.
Click OK.
The HART Edit dialog box is closed and the settings are saved to the
new block.
38
Reset Configuration Changed Flag
40
Enter/Exit Fixed Primary Variable Current Mode
Only Use in HART TRIG block
44
Write Primary Variable Units
Only Use in HART TRIG block
48
Read additional Transmitter Status
54
Read Transmitter Variable Information
59
Write Number Of Response Preambles
Only Use in HART TRIG block
Effective values of HART commands (Continued)
Effective Value
HART Commands
Effective Value
IMPORTANT
Command 0 must be configured for each HART device in
order for the other commands to work.
TIP
The register range is 40003…49999 for 1758-RTU
controllers, and 40003…47999 for 1758-FLO controllers.
Description of HART Commands on page 213
for
more information on the Send, Return, Unit, and HART
State Addr registers.