DataSite Flow Configuration Utility (DS FloConfig) 125
Meter Run
This is the meter run number.
Flow Rate
These are the measurements for gas flow rate.
•
Volume Rate (Base)
Volume transient flow rate (ft3/hour) at base conditions. For
information on settings for the base pressure and temperature, see
Instrument Parameters for AGA3 Standard on page 137 and
Parameters for AGA7 Standard on page 139
•
Volume Rate (Flowing)
Volume transient flow rate (ft3/hour) at flowing conditions. Flowing
conditions means the actual pressure and temperature.
•
Mass Rate
Mass transient flow rate (lbm/hour).
Process Measurements
These are the process measurements:
•
Static Pressure
Absolute or gauge, depending on the static pressure type settings in
Instrument Parameters for AGA3 Standard on page 137 and
Parameters for AGA7 Standard on page 139
•
Temperature
Temperature of the fluid while it is flowing.
•
Differential Pressure (for AGA3)
Difference between the pressure at the upstream and the pressure at the
downstream.
•
Pulse (for AGA7)
Pulse count accumulated in a second.