Command number 21: reset accumulation – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 308

Publication 1758-UM002D-EN-P - October 2010
308 Extension Modbus Protocol for DataSite Controllers (1758-FLO)
There is no event code for command number 20.
Command Number 21: Reset Accumulation
Use command number 21 to clear accumulation to zero for one meter run.
There is no event code for command number 21.
Return codes for command number 20
Return Code
Description
00
OK
01
Meter run is invalid
100
Pass code is incorrect
Other
Invalid
Parameters for command number 21
Address
Data Type
Attribute
Description
49025
u_short
RW
21
49026
u_short
R
Return code
49027
u_short
W
Meter run (0…7)
49028
u_int
W
Pass code for user
Return codes for command number 21
Return Code
Description
00
OK
01
Meter run is invalid
100
Pass code is incorrect
Other
Invalid