Register addresses, 1758-flo datasite variables, Register addresses 1758-flo datasite variables – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 324

Publication 1758-UM002D-EN-P - October 2010
324 Enron Modbus Protocol for the 1758-FLO DataSite Controller
Register Addresses
The following table lists the address ranges of the Enron registers that hold
short integers, long integers, and single precision floats.
1758-FLO DataSite
Variables
A 1758-FLO DataSite controller supports up to eight meter runs.
Meter runs are configured individually. Gas quality is set for each meter run.
The following table lists the ranges of Enron Modbus variables used by the
controller.
Register address ranges
Range
Data Type
Description
32
Record
Event/Alarm archive
(Event from 1…700, alarm from 701…1000)
701…716
Record
Hourly/Daily archive
1001…2999
Boolean
Reserved
3001…3450
Short integer
16 bits, high byte first
5001…5080
Long integer
32 bits, high byte fist, high word first. For example,
if the number 2,923,517,522 sent a 32-bit
unsigned integer, it would be AE 41 56 52.
7001…7800
Float
32 bits, IEEE single precision floating-point
number, high byte first, high word first. For
example, if the number 326,787 is sent as a 32-bit
float, it would be 48 9F 90 60.
Enron Modbus variable ranges
Purpose
Hourly/Daily Archive
Boolean
Short Integer
Long Integer
Floating Point
System variables
None
None
3000…3050
None
None
Meter run 0
701…702
None
3051…3100
5001…5010
7001…7100
Meter run 1
703…704
None
3101…3150
5011…5020
7101…7200
Meter run 2
705…706
None
3151…3200
5021…5030
7201…7300
Meter run 3
707…708
None
3201…3250
5031…5040
7301…7400
Meter run 4
709…710
None
3251…3300
5041…5050
7401…7500
Meter run 5
711…712
None
3301…3350
5051…5060
7501…7600
Meter run 6
713…714
None
3351…3400
5061…5070
7601…7700
Meter run 7
715…716
None
3401…3450
5071…5080
7701…7800