Page 277

Publication 1758-UM002D-EN-P - October 2010
Extension Modbus Protocol for DataSite Controllers (1758-FLO) 277
Modbus Registers for the Power Shutdown Time
These registers record the previous shutdown time of the controller.
Modbus Registers for Reading Gas Component Parameters
The gas component parameters can be read from a gas component analyzer
automatically by using Modbus Master scan blocks. Refer to
for details on using the Modbus Master scan block. The registers on the
following table are used for saving the parameters read from the gas
component analyzer.
Modbus registers for power shutdown time
Description
Data Type
Modbus Address
Hour for power off
u_short
32911
Minute for power off
u_short
32912
Second for power off
u_short
32913
Modbus registers for reading gas component parameter
Modbus Addresses in 1758-FLO Controller
Description
Datasite FLO used
register
user defined register
when using Modbus
Master Scan
32159…32200
48001…48050
Component of meter run 0 (see
)
32259…32300
48051…48100
Component of meter run 1
32359…32400
48101…48150
Component of meter run 2
32459…32500
48151…48200
Component of meter run 3
32559…32600
48201…48250
Component of meter run 4
32659…32700
48251…48300
Component of meter run 5
32759…32800
48301…48350
Component of meter run 6
32859…32900
48351…48400
Component of meter run 7
Offset structure table
Data Type
Offset
Name
Description
float
0
CH4
Methane
float
1
N2
Nitrogen
float
2
CO2
Carbon dioxide
float
3
C2H6
Ethane