Command number 2: set the pass code – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 284
![background image](/manuals/579221/284/background.png)
Publication 1758-UM002D-EN-P - October 2010
284 Extension Modbus Protocol for DataSite Controllers (1758-FLO)
Command Number 2: Set the Pass Code
Use command number 2 to set a new pass code. The default pass code is 0.
There is no event code for command number 2.
Return codes for command number 1
Return Code
Description
00
OK
01
Year invalid
02
Month invalid
03
Day invalid
04
Hour invalid
05
Minute invalid
06
Second invalid
07
Week invalid
100
Pass code is wrong
Other
Invalid
Parameters for command number 2
Address
Data Type
Attribute
Description
49025
u_short
RW
2
49026
u_short
R
Return code
49027
u_short
W
Reserved
49028
u_int
W
Pass code for user
Default is 0.
49030…49034
—
—
Reserved
49035
u_int
W
New pass code
Return codes for command number 2
Return Code
Description
00
OK
100
Pass code is incorrect
Other
Invalid