Download the configuration file – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 256
![background image](/manuals/579221/256/background.png)
Publication 1758-UM002D-EN-P - October 2010
256 DataSite DNP3 Configuration Utility (DS DNP3)
5.
If you want the host computer to check the RTC of the DataSite
controller periodically, select the Time Synchronization box. Then, in
the Interval box, specify how often you want the host computer to
check the RTC of the controller. The value range of the Interval
parameter is 0…999999999 and the default value is 1800000. Interval
parameter is 0 when you select the At Start Up Only check box.
6.
Enter the values for the DI, AI, and String events accordingly.
Download the Configuration file
For a new DNP3 configuration to take effect, the configuration file needs to
be downloaded to the DataSite controller after editing.
Follow this step to download the DNP3 configuration.
•
From the Control menu, choose Download.
You can also click the Download button
on the toolbar.
40
3
Short floating-point analog output state
50
0
Time and date
50
1
Time and date
51
1
Time and date CTO
80
1
Internal indications
110
String
length
Octet string object
111
String
length
Octet string event object
Event parameters
Parameter
Description
Range of Options or Values
Event mode
Event reporting mode
Last value: Only one event is retained
in the buffer for each point.
Queue: All events will be retained.
Event buffer
length
Maximum number of events
buffered by the controller
0…2000 for DI and AI events.
0…10 for String events.
Event scan time
Interval of the controller
scanning the events
0…99999
SDNP3 object library (Continued)
Object No.
Variant No. Description