Command number 9: set up the input signal test – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 289

Publication 1758-UM002D-EN-P - October 2010
Extension Modbus Protocol for DataSite Controllers (1758-FLO) 289
There is no event code for command number 8.
Command Number 9: Set Up the Input Signal Test
Use command number 9 to set up the input signal test for one meter run.
49035
u_short
R
Contract hour (0…23)
49036
u_short
R
Contract minute (0…59)
49037
u_short
—
Reserved
Return codes for command number 8
Return Code
Description
00
OK
100
Pass code is wrong
Other
Invalid
Parameters for command number 9
Address
Data Type
Attribute
Description
49025
u_short
RW
9
49026
u_short
R
Return code
49027
u_short
W
Meter run (0…7)
49028
u_int
W
Pass code for user
49030…49034
—
—
Reserved
49035
u_short
W
Whether differential pressure or
pulse tested.
0: No test
1: Test
49036
u_short
W
Whether static pressure tested.
0: No test
1: Test
49037
u_short
W
Whether temperature tested.
0: No test
1: Test
49038
float
W
Differential pressure or pulse test
value
49040
float
W
Static pressure test value
49042
float
W
Temperature test value
Parameters for command number 8 (Continued)