140 DataSite Flow Configuration Utility (DS FloConfig)
For descriptions on these parameters, see
•
Cut-off Pulse
When the pulse of the turbine meter during the base multiplier period
(BMP) is lower than the value entered in the Cut-off Pulse box, the
DataSite controller will consider any flow as inexistent.
There will be a cutoff alarm in the Meter Run window, and the flow
rates become zero when this happens.
Configure Field Signal Parameters for the AGA3 Standard
If you have chosen the AGA3 standard, you need to configure the parameters
for the field signals accordingly.
TIP
For any changes to parameter settings to be applied to the
DataSite controller, you need to click Download.
IMPORTANT
Before downloading any changes to the DataSite controller,
it is recommended that you perform an upload. This helps
prevent modifying information that you did not intend to
change.