Command number 27: read new event logs – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 317
Publication 1758-UM002D-EN-P - October 2010
Extension Modbus Protocol for DataSite Controllers (1758-FLO) 317
There is no event code for command number 26.
Command Number 27: Read New Event Logs
Use command number 27 to read the new event records. The value in register
49030 indicates how many new event records have been loaded with this
reading. The maximum number is 20. Each new event record consists of 10
registers and has the same format as an event.
49195…49204
See above
See above
Event 17
49205…49214
See above
See above
Event 18
49215…49224
See above
See above
Event 19
49225…49234
See above
See above
Event 20
Return codes for command number 26
Return Code
Description
00
OK
01
Event start index is invalid
02
Event numbers is invalid
100
Pass code is incorrect
Other
Invalid
Parameters for command number 27
Address
Data Type
Attribute
Description
49025
u_short
RW
27
49026
u_short
R
Return code
0: OK
49027
u_short
W
Reserved
49028
u_int
W
Pass code for user
49030
u_short
R
Number of read records
49031
u_short
R
Number of remaining new records
49032
u_short
R
Number of lost records
49033…49034
—
—
Reserved
Registers for events 2…20 (Continued)
Address
Data Type
Attribute
Description