180 DataSite Flow Configuration Utility (DS FloConfig)
Calibrate the Meter Sensor
The Meter Calibration function allows you to maintain continuous
measurement of the flow rate by the flow meter while calibrating field sensors.
You can do this by sending forced signals to the flow meter to replace the field
signals from the sensors.
You need to calibrate the meter sensor in the following situations:
•
when the sensor does not work but the meter is required to accumulate
measurements continuously.
•
when the sensor needs to be checked for its accuracy.
Open the Force Signals dialog box
Follow this step to open the Force Signals dialog box.
•
From the Operation menu, choose Meter Calibration.
The Force Signals dialog box appears.
Set Forced Values for Field Signals
Follow these steps to set forced values for the field signals you want to
calibrate.
1.
In the Force Signals dialog box, select the meter run.
2.
Select the check box for the field signal(s).
You may select more than one signal for calibration.