Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual
Page 23
Publication 1758-UM002D-EN-P - October 2010
DataSite Configuration Settings Utility (DS Settings) 23
This table shows the options and/or value range available for each
parameter.
3.
To save the settings and close the Serial Ports Settings dialog box, click
OK.
To close the dialog box without saving the settings, click Cancel.
4.
Click Download.
The new settings are applied to the DataSite controller.
The following sections provide more information on some of the parameters
for the serial port.
Protocol
When customizing the communication protocol, it is recommended that you
set the protocol as "None". You can then use flags in DataSite Workbench to
program the customized communication protocol. The flags corresponding to
each serial port are shown in the following table:
Serial port parameters
Parameter
Parameter Options or Value Range
COM
COM1, COM2
Station
1…247
Protocol
Modbus RTU, Modbus ASC, DS Workbench (only for
COM2), None
Master/Slave state
Master, Slave
Duplex
Full, Half
Baud rate
2400, 4800, 9600, 14400, 19200, 38400, 56000, 57600
Parity
Even, Odd, None
Data bits
7, 8
Stop bits
1, 2
Port type
RS232, RS485
Timeout (in units of 10 ms)
1…1000
Delay time (in units of 10 ms)
0…300
Flags in DataSite Workbench for serial ports
Flag
Description
US1_RX
US1 receiving task for US1 customized protocol
US2_RX
US2 receiving task for US2 customized protocol