5 mains fuses, Mains fuses, Appendix – Lenze ECSCAxxx User Manual
Page 464
Appendix
Overview of accessories
l
464
EDBCSXA064 EN 3.2
14.8.5
Mains fuses
ƒ
Mains fuses are not included in the Lenze delivery program. Use standard fuses.
ƒ
When using ECSxE power supply modules which are fused on the supply side the
DC−bus supply need not be fused.
ƒ
When ECS axis modules are supplied by devices of the 82xx and 93xx series with a
continuous DC current > 40 A, install the following fuses between the supplying
device and the ECS devices:
Fuse
Support
Value [A]
Lenze type
Lenze type
50
EFSGR0500ANIN
EFH20007
ƒ
Observe the national and regional regulations (VDE, UL, EVU, ...).
J
Warnings!
ƒ
Use UL−approved cables, fuses and fuse holders only.
ƒ
UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"