4 changing and saving parameters, Changing and saving parameters, Parameter setting – Lenze ECSCAxxx User Manual
Page 154: Stop
Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Changing and saving parameters
l
154
EDBCSXA064 EN 3.2
7.3.4
Changing and saving parameters
All parameters for the axis module/power supply module parameterisation or monitoring
are stored in codes. The codes are numbered and marked with a "C" in the documentation.
Some codes store the parameters in numbered "subcodes" to provide a clear structure for
parameter setting (e.g. C0517 user menu).
(
Stop!
Your settings have an effect on the current parameters in the main memory.
You must store your settings as a parameter set to prevent that they will get
lost when switching the mains!
Step
Keys
Action
1.
Select menu
z y Z Y
Select the desired menu with arrow keys.
2.
Change to code level
Z
Display of first code in the menu
3.
Select code or subcode
y z
Display of the current parameter value
4.
Change to parameter level
V
5.
If SHPRG is displayed, inhibit
controller
S
The drive is coasting.
6.
Change parameter
A
Z Y
Move cursor under the digit to be changed
B
y z
Change digit
T y
T z
Change digit quickly
7.
Accept changed parameter
Display SHPRG or SHPRG
p T V
Confirm change to accept parameter
Display "OK"
Display
p −
The parameter was accepted immediately.
8.
If necessary, enable controller
U
The drive should be running again.
9.
Change to code level
A
V
Display of operating level
B
V
Display of the code with changed parameters
10. Change further parameters
Restart the "loop" at step 1. or step 3.
11. Save changed parameters
A
z y Z Y
Select Code C0003 "PAR SAVE" in the menu
"Load/Store"
B
V
Change to parameter level
Display "0" and "Ready"
Select parameter set in which the
parameters are to be saved
permanently
C
Z
Save as parameter set 1:
ð set "1" "Save PS1"
D
T V
When "OK" is displayed, the settings are permanently
saved.
12. Change to code level
A
V
Display of operating level
B
V
Display C0003 "PAR SAVE"