1 fault responses, Monitoring functions – Lenze ECSCAxxx User Manual
Page 197
Monitoring functions
Fault responses
l
197
EDBCSXA064 EN 3.2
10.1
Fault responses
Response
ð Consequence
Display
Keypad XT
RDY
IMP
Fail
TRIP
o
n
n
TRIP active:
ð The power outputs U, V, W are switched to high resistance.
ð The drive is coasting (no control).
TRIP reset:
ð The drive decelerates to its setpoint within the set deceleration
times.
Message
Danger!
The drive restarts automatically if the message is removed.
o
n
n
Message active:
ð The power outputs U, V, W are switched to high resistance.
£ 0.5 s ð The drive is coasting (no control).
> 0.5 s
ð The drive is coasting (due to internal controller inhibit). If
necessary, restart program.
Message reset:
ð The drive runs to its setpoint with the maximum torque.
FAIL−QSP
ð The drive is decelerated to standstill within the quick stop
deceleration time (C0105).
˘
˘
n
Warning
STOP!
The drive can be destroyed due to deactivated monitoring
functions.
n
o
n
ð The failure merely is displayed, the drive runs on in a controlled
manner.
Off
STOP!
The drive can be destroyed due to deactivated monitoring
functions.
˘
˘
˘
ð There is no response to the failure.
o = off
n = on
Responses (
¶ 197) of monitoring functions can be parameterised partly via codes ˘ in the
GDC parameter menu under Monitoring.