System modules
DIGITAL_IO (node number 1)
Outputs_DIGITAL (digital outputs)
l
346
EDBCSXA064 EN 3.2
Codes
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0118
Polarity of the digital outputs
^ 345
^ 129
1 DIGOUT pol
0
HIGH level active
X6/DO1 (DIGOUT_bOut1_b)
2 DIGOUT pol
0
HIGH level active
X25 (DIGOUT_bRelais_b, brake
connection)
0
HIGH level active
1
LOW level active
C0444
Status of the digital outputs
Only display
^ 345
1 DIS: DIGOUT
0
1 Status of the digital output
X6/DO1
2 DIS: DIGOUT
Relay control status
C0602 MONIT REL1
3
Fault response − open circuit
monitoring of relay output X25
0
TRIP
2
Message
3
Off
4
FAIL−QSP
Terminal assignment
Digital
inputs
Function
Electrical data
X6
Digital output
24 V DC
0.7 A (max. 1.4 A)
short−circuit−proof
X6/DO1
Digital output 1
X6
Output "safe torque off" (former "safe standstill")
X6/SO
Output feedback
LOW
During operation
HIGH "Safe torque off" (former
"safe standstill") active
X25
Connection motor holding brake
23 ... 30 V DC;
max. 1.5 A
Set the brake voltage so that the
permissible voltage at the brake
will not be exceeded or the values
do not fall below the threshold!
X25/B1
Brake connection +
X25/B2
Brake connection −
X6
Low−voltage supply motor holding brake
X6/B+
Brake supply +
X6/B−
Brake supply −