Appendix – Lenze ECSCAxxx User Manual
Page 427
Appendix
Code table
l
427
EDBCSXA064 EN 3.2
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C2461
Detected load
CANaux_IN/CANaux_OUT (CAN
bus interface X14)
Read only
A faultless operation is only
guaranteed if the total bus load
of all connected nodes amounts
to a value
£ 80 %.
^ 179
1 Load IN/OUT
0
{1 %}
100 All sent telegrams
2 Load IN/OUT
All received telegrams
3 Load IN/OUT
Sent to CANaux1_OUT
4 Load IN/OUT
Sent to CANaux2_OUT
5 Load IN/OUT
Sent to CANaux3_OUT
6 Load IN/OUT
Sent to parameter data
channel 1
7 Load IN/OUT
Sent to parameter data
channel 2
8 Load IN/OUT
Received from CANaux1_IN
9 Load IN/OUT
Received from CANaux2_IN
10 Load IN/OUT
Received from CANaux3_IN
11 Load IN/OUT
Received from parameter data
channel 1
12 Load IN/OUT
Received from parameter data
channel 2
C2466 Sync Response
1
CAN sync response for interface
X14 (CAN−AUX)
The value "1" should always be
set!
0
No response
1
Response
C2467 Sync Rx ID
128
CAN−AUX sync receipt ID for CAN
bus interface X14
^ 168
1
{1}
256
C2468 Sync Tx ID
128
CAN−AUX Sync−transmission ID
for CAN bus interface X14
^ 442
^ 169
1
{1}
256
C2469 Sync Tx time
0
CAN−AUX sync transmission cycle
for CAN bus interface X14
A sync telegram with the
identifier of C2468 is sent with
the set cycle time.
^ 166
^ 163
0
{1 ms}
65000 0 = switched off
C2470 ParWrite
0
CANaux channel used by
L_ParWrite/L_ParRead
(byComChannel = 11)
^ 180
0
Unused PDO channel free for
reconfiguration
(CANaux1...3_IN/CANaux1...3_OUT)
1
Parameter data channel 2