System bus (can / can−aux) configuration – Lenze ECSCAxxx User Manual
Page 181

System bus (CAN / CAN−AUX) configuration
Remote parameterisation (gateway function)
l
181
EDBCSXA064 EN 3.2
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C0603 MONIT CE5
3
Fault response − gateway
function monitoring (CE5)
"Timeout" when remote
parameter setting (C0370) is
activated via interface X4 (CAN)
^ 202
^ 180
0
TRIP
2
Warning
3
Off
C2118 ParWriteChan
.
0
CAN object for L_ParRead and
L_ParWrite
(byComChannel = 10)
^ 180
0
Unused PDO channel free for
reconfiguration
(CAN1...3_IN/CAN1...3_OUT)
1
Parameter data channel 2
C2470 ParWrite
0
CANaux channel used by
L_ParWrite/L_ParRead
(byComChannel = 11)
^ 180
0
Unused PDO channel free for
reconfiguration
(CANaux1...3_IN/CANaux1...3_OUT)
1
Parameter data channel 2
C2485 MONIT CE15
3
Fault response − gate function
monitoring (CE15)
"Timeout" when remote
parameterisation (C0370) is
activated via interface X14
(CAN−AUX)
^ 202
^ 180
0
TRIP
2
Warning
3
Off