System modules – Lenze ECSCAxxx User Manual
Page 290
System modules
CAN2_IO (node number 32)
l
290
EDBCSXA064 EN 3.2
Codes
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0356
CAN time settings for CAN bus
interface X4
^ 163
1 CAN times
3000
0
{1 ms}
65000 CAN boot−up time:
Delay time after mains
connection for initialisation
through the master.
2 CAN times
0
CAN2...3_OUT cycle times:
Factor for the task time to send
process data telegram.
0 = event−controlled
transmission
3 CAN times
0
4 CAN times
20
Delay time for initial
transmission of the process data
objects 2 and 3 after the CAN bus
changed to "Operational"
C0357
Monitoring time for CAN1...3_IN
(CAN bus interface X4)
^ 202
1 CE monit time
3000
1
{1 ms}
65000 CE1 monitoring time
2 CE monit time
3000
CE2 monitoring time
3 CE monit time
3000
CE3 monitoring time
C0863
Digital process data input words
for CAN bus interface X4
Hexadecimal value is bit−coded.
Read only
^ 446
0000
{hex}
FFFF
1 CAN IN bits
Bit 0
...
Bit15 CAN1_IN: Process data input
word 1
2 CAN IN bits
Bit 16
...
Bit 31 CAN1_IN: Process data input
word 2
3 CAN IN bits
Bit 0
...
Bit15 CAN2_IN: Process data input
word 1
4 CAN IN bits
Bit 16
...
Bit 31 CAN2_IN: Process data input
word 2
5 CAN IN bits
Bit 0
...
Bit15 CAN3_IN: Process data input
word 1
6 CAN IN bits
Bit 16
...
Bit 31 CAN3_IN: Process data input
word 2
C0866
Analog process data input words
(decimal) for CAN bus interface
X4
100.00% = 16384
Read only
^ 446
1 CAN IN words
−199.99
{0.01 %}
199.99 CAN1_IN word 1
2 CAN IN words
CAN1_IN word 2
3 CAN IN words
CAN1_IN word 3
4 CAN IN words
CAN2_IN word 1
5 CAN IN words
CAN2_IN word 2
6 CAN IN words
CAN2_IN word 3
7 CAN IN words
CAN2_IN word 4
8 CAN IN words
CAN3_IN word 1
9 CAN IN words
CAN3_IN word 2
10 CAN IN words
CAN3_IN word 3
11 CAN IN words
CAN3_IN word 4