2 outputs_aif_management, Outputs_aif_management, System modules – Lenze ECSCAxxx User Manual
Page 258
System modules
AIF_IO_Management (node number 161)
Outputs_AIF_Management
l
258
EDBCSXA064 EN 3.2
13.1.2
Outputs_AIF_Management
This SB serves to transfer command and messages to a fieldbus module connected to an
automation interface (AIF).
For this purpose, a control word is available via C2120. The commands are given as
numbers. Some command numbers generally apply to all fieldbus modules, others only
apply to single fieldbus modules. A total of 16 commands can be made available.
,
Please read the documentation for the connected fieldbus module.
Bit 7
Toggle-Bit (MSB)
Bit 8 … 15
AIF control word
Outputs_AIF_Management
AIF_wControl
C2120
Bit 0 … 6
ECSXA243
Fig. 13−2
System block "Outputs_AIF_Management"
System variables
Variable
Data
type
Signal
type
Address
Display
code
Display
format
Notes
AIF_wControl
Word
˘
%QX161.0
C2120
˘
Codes
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C2120 AIF: Control
0
AIF−CAN: control word
^ 258
0
{1}
255 Binary interpretation reflects bit
states
0
No command
Note: The MSB (bit 7) of the
control word automatically
changes its state with every
access to the code. Observe this
when interpreting the data!
1
Read XCAN codes + reinitialisation
2
Read XCAN code
10
Read XCAN C2356/1 ... 4
11
Read XCAN C2357
12
Read XCAN C2375
13
Read XCAN C2376 ... C2378
14
Read XCAN C2382
255
Not assigned