DFOUT_IO_DigitalFrequency (node number 22)
Inputs_DFOUT / Outputs_DFOUT
l
341
EDBCSXA064 EN 3.2
13.17.1.2
Configuration master frequency output signal
You configure the type of the master frequency output signal via C0540:
C0540 = 0
Output of an analog signal
Function
The input signal DFOUT_nOut_vis interpreted as an analog signal [%] and is output as a
frequency signal on the master frequency output X8.
Scaling
100 %
º (INT)16384 º C0011 (n
max)
Transmission
function
f [Hz]
+ DFOUT_nOut_v [%] @ C0030
100 @
C0011 (n
max
)
60
DFOUT_nln_v
+ f [Hz] @ 60
C0030 @
2
14
15000
Example
l
DFOUT_nOut_v = 50 %
l
C0030 = 3, this corresponds to a number of increments of 2048 increments/revolution
l
C0011 = 3000 rpm
f [Hz]
+ 50 % @ 2048
100 @
3000
60
+ 51200 Hz
C0540 = 1
Output of a speed signal
Function
The input signal DFOUT_nOut_vis interpreted as a speed signal [rpm] and is output as a
frequency signal on the master frequency output X8.
Scaling
15000 rpm
º (INT)16384
Transmission
function
f [Hz]
+ DFOUT_nOut_v [rpm] @ C0030
60
Example
l
DFOUT_nOut_v = 3000 rpm
l
C0030 = 3, this corresponds to a number of increments of 2048 increments/revolution
f [Hz]
+ 3000 rpm @ 2048
60
+ 102400 Hz
C0540 = 2
Encoder simulation of the resolver with zero track in resolver position
Function
l
The function is used if a resolver is connected to X7.
l
The encoder constant for output X8 is set in C0030.
l
The output of the zero pulse with reference to the rotor depends on how the resolver is
mounted to the motor.
l
The zero pulse can be shifted by +360 ° via C0545 (65536 inc = 360 °).
)
Note!
The zero pulse can only be output with C0540 = 2 (encoder simulation of
resolver).