Appendix – Lenze ECSCAxxx User Manual
Page 456
Appendix
General information about the system bus (CAN)
Parameter data transfer
l
456
EDBCSXA064 EN 3.2
14.7.4.3
Examples of the parameter data telegram
Reading parameters
The heatsink temperature C0061 ( 43 °C) is to be read from the controller with node
address 5 via the parameter data channel 1.
ƒ
Identifier calculation
Identifier from SDO1 to controller
Calculation
1536 + node address
1536 + 5 = 1541
ƒ
Command "Read Request" (request to read a parameter from the controller)
Command
Value [hex]
Read request
0x40
ƒ
Index calculation
Index
Calculation
24575 − code number
24575 − 61 = 24514 = 0x5FC2
ƒ
Subindex: 0
ƒ
Telegram to controller
Identifier
User data
Command
Index
LOW byte
Index
HIGH byte
Subindex
Data 1
Data 2
Data 3
Data 4
1541
0x40
0xC2
0x5F
0x00
0x00
0x00
0x00
0x00
ƒ
Telegram from controller
Identifier
User data
Command
Index
LOW byte
Index
HIGH byte
Subindex
Data 1
Data 2
Data 3
Data 4
1413
0x43
0xC2
0x5F
0x00
0xB0
0x8F
0x06
0x00
– Command:
"Read Response" (response to the read request) = 0x43
– Identifier:
SDO1 from controller (1408) + node address (5) = 1413
– Index of the read request:
0x5FC2
– Subindex:
0
– Data 1 ... 4:
0x00068FB0 = 430000
W 430000 : 10000 = 43 °C