File of retransmission output – Yokogawa DAQWORX User Manual
Page 89

4-42
IM WX102-01E
File of Retransmission Output
Set the time constant for abrupt changes in voltage or current being output from the
transmission output module.
Choose a transmission output time constant from the pull down menu. The setting values
and corresponding time constants are as follows:
Value
Time Constant (ms)
Value
Time Constant (ms)
0
4
5
250
1
12
6
500
2
28
7
950
3
60
8
1750
4
125
0
3000
Note
The time constant is for changes from 1 to 5 V, and 4 to 30 mA. If that change is smaller, the
actual time constant will be smaller than the set time constant.
4.19 Setting A/D Converter Integration Time, Filter, and Scan Interval