Index
Before Operation
• Resistance temperature detector (RTD)
RTD Type
Display
Measurable Range
Pt100:1mA
PT1
–200.0 to 600.0°C
Pt100:2mA
PT2
–200.0 to 250.0°C
JPt100:1mAJ
JPT1
–200.0 to 550.0°C
JPt100: 2mAJ
JPT2
–200.0 to 250.0°C
Pt50: 2mAJ
PT50
–200.0 to 550.0°C
Ni100:1mA-S
*1
NI1
–200.0 to 250.0°C
Ni100:1mA-D
*2
NI2
–60.0 to 180.0°C
Ni120:1mA
*3
NI3
–70.0 to 200.0°C
Cu10: GE
*4
CU1
–200.0 to 300.0°C
Cu10: L&N
*4
CU2
–200.0 to 300.0°C
Cu10: WEED
*4
CU3
–200.0 to 300.0°C
Cu10: BAILEY
*4
CU4
–200.0 to 300.0°C
Pt100:1mA-H
PT1S
–140.00 to 150.00°C
Pt100: 2mA-H
PT2S
–70.00 to 70.00°C
JPt100:1mA-H
JPT1S
–140.00 to 150.00°C
JPt100: 2mA-H
JPT2S
–70.00 to 70.00°C
J263*B
J263B
–0.0 to 300.0K
*1 RTD (SAMA)
*2 RTD (DIN)
*3 RTD (McGROW EDISON COMPANY)
*4 RTD (Cuid)
Guaranteed accuracy range
Cu10: GE
–84.4 to 170.0°C
Cu10: L&N
–75.0 to 150.0°C
Cu10: WEED
–20.0 to 250.0°C
Cu10: BAILEY
–20.0 to 250.0°C
• Contact point (DI)
Input Type
Display
Measurable Range
VOLT
LEVL
0 to 1
*1
CONTACT
CONT
0 to 1
*2
*1 OFF if below 2.4V, ON if above 2.4V
*2 Contact point ON/OFF
• mA input (mA)
Measurement Range
Display
Measurable Range
20mA
20mA
–20.000 to 20.000mA
• Pulse input (PULSE)
Measurement Range
Measurable Range
RATE
Determine the count number during 1s interval.
GATE
Determine the most occurring state, ON or OFF, during 1s
interval.
• Power monitor (AC)
Input Range
Display
250V-0.5A
250V-0.5A
250V-5A
250V-5A
25V-0.5A
25V-0.5A
25V-5A
250V-5A
• Strain input (STRAIN)
Measurement Range
Display
Measurable Range
2k
2k
–2000.0 to 2000.0µε
20k
20k
–20000 to 20000µε
200k
200k
–20000 to 20000µε
1.5 DA100 Functions