Modbus – IAI America ROBO Cylinder Series User Manual
Page 93

5. Modbus RTU
85
Modbus
5.3.10 I/O Port Output Signal Status Reading<
(1) Function
This query reads the port output value of the RC controller regardless of the PIO pattern.
(2) Query format
Field
Number of data items
(number of bytes)
RTU mode
8-bit data
Remarks
Start
None
Silent interval
Slave address [H]
1
Arbitrary
Axis number + 1 (01
H
to 10
H
)
Function code [H]
1
03
Register reading
Start address [H]
2
9004
Output port monitor register
Number of registers [H]
2
0001
Reading addresses 9004
H
Error check [H]
2
CRC (16 bits)
End
None
Silent interval
Total number of bytes
8
(3) Response format
A response message contains 16 bits of data per register.
Field
Number of data items
(number of bytes)
RTU mode
8-bit data
Remarks
Start
None
Silent interval
Slave address [H]
1
Arbitrary
Axis number + 1 (01
H
to 10
H
)
Function code [H]
1
03
Register reading
Number of data bytes [H]
1
02
Reading 1 register = 2 bytes
Data 1 [H]
2
D0 output value
Port output value [Hex]
Error check [H]
2
CRC (16 bits)
End
None
Silent interval
Total number of bytes
7