Modbus – IAI America ROBO Cylinder Series User Manual
Page 316
7. T
roubleshooting
308
Modbus
Continued from the previous page
Cannot communicate with specific controllers.
[1] Wrong wiring of communication cables between controllers and junction o Check wiring *3
[2] Device power supply error o Check power supply voltage o Check that the 0 V line is used
commonly for all devices o Use the 0 V line commonly for all devices.
Cannot communicate from time to time?
[1] Malfunction due to noise o
(1) Decrease the communication speed Check *2
(2) Change communication cable wiring Check *7
(3) Check connection of FG of each RC controller *7
(4) Mount a clamp filter on the power lines
(5) Check grounding of the control board *7
[2] Inadequate host programs o
Check programs again (occurrence of communication buffer overflow, etc.?)
- ERC2 (138 pages)
- ERC2 (188 pages)
- ERC3 (438 pages)
- ERC (153 pages)
- RCA-E (53 pages)
- RCA-P (42 pages)
- RCB-101-MW (38 pages)
- RCP2-C (178 pages)
- RCS-E (102 pages)
- RCA-A4R (72 pages)
- RCA-RA3C (114 pages)
- RCA-SRA4R (56 pages)
- RCA2-RA2AC (100 pages)
- RCA2-SA2AC (92 pages)
- RCA2-TA4C (134 pages)
- RCD-RA1D (40 pages)
- RCP2-BA6 (72 pages)
- RCP2-GRSS (130 pages)
- RCP2-HS8C (126 pages)
- RCP2-RA2C (120 pages)
- RCP2-RTBS (80 pages)
- RCP2W-SA16C (46 pages)
- RCP3-RA2AC (60 pages)
- RCP4-RA5C (82 pages)
- RCP4-SA5C (94 pages)
- RCP4W (96 pages)
- RCS2-F5D (142 pages)
- RCS2-GR8 (46 pages)
- RCS2-RN5N (80 pages)
- RCS2-RT6 (60 pages)
- RCS2-SA4C (258 pages)
- RCS2-TCA5N (62 pages)
- RCL-SA1L (66 pages)
- RCL-RA1L (56 pages)
- RCLE-GR5L (46 pages)
- IK Series (16 pages)
- FS (84 pages)
- IF (76 pages)
- ISB (114 pages)
- ISDA (126 pages)
- ISDB (116 pages)
- ISPWA (90 pages)
- NS (78 pages)
- ICS(P)A (16 pages)
- RS (46 pages)