Modbus – IAI America ROBO Cylinder Series User Manual
Page 224
6. Modbus
ASCII
216
Modbus
(4) Sample query
A sample query that reads the device status 2 (address 9006
H
) in a controller of axis No. 0 is shown
below.
Query: 01 03 90 06 00 01 65 [CR] [LF]
Field
ASCII mode
fixed character string
Converted ASCII
code data [H]
Start
‘:’
3A
Slave address [H]
‘0’, ‘1’
3031
Function code [H]
‘0’, ‘3’
3033
Start address [H]
‘9’, ‘0’, ‘0’, ‘6’
39303036
Number of registers [H]
‘0’, ‘0’, ‘0’, ‘1’
30303031
Error check [H]
‘6’, ‘5’ (In accordance with LRC calculation) 3635
End
‘CR’, ‘LF’
0D0A
The response to the query is as follows.
Response: 01 03 02 80 00 7A [CR] [LF]
Field
ASCII mode
fixed character string
Converted ASCII
code data [H]
Start
‘:’
3A
Slave address [H]
‘0’, ‘1’
3031
Function code [H]
‘0’, ‘3’
3033
Number of data bytes [H]
‘0’, ‘2’ (2 bytes = 1 register)
3032
Data 1 [H]
‘8’, ‘0’, ‘0’, ‘0’
38303030
Error check [H]
‘7’, ‘A’ (In accordance with LRC calculation) 3741
End
‘CR’, ‘LF’
0D0A
Note The data of the response example is simply an example and will vary depending on
various conditions.