5. Modbus RTU
103
Modbus
5.3.18 Total Time after Power On Reading <
(1) Function
This bit reads the total time since the controller power was turned on. The unit is ms.
The timer value is not cleared by software reset.
(2) Query format
Field
Number of data items
(number of bytes)
RTU mode
8-bit data
Remarks
Start
None
Silent interval
Slave address [H]
1
Arbitrary
Axis number + 1 (01
H
to 10
H
)
Function code [H]
1
03
Register reading
Start address [H]
2
9010
System timer
Number of registers [H]
2
0002
Reading addresses 9010
H
to
9011
H
Error check [H]
2
CRC (16 bits)
End
None
Silent interval
Total number of bytes
8
(3) Response format
A response message contains 16 bits of data per register.
Field
Number of data items
(number of bytes)
RTU mode
8-bit data
Remarks
Start
None
Silent interval
Slave address [H]
1
Arbitrary
Axis number + 1 (01
H
to 10
H
)
Function code [H]
1
03
Register reading
Number of data bytes [H]
1
04
Reading 2 registers = 4 bytes
Data [H]
4
System timer
System timer [Hex]
The unit is ms.
Error check [H]
2
CRC (16 bits)
End
None
Silent interval
Total number of bytes
9