Data and status reading (queries using code 03), Modbus – IAI America ROBO Cylinder Series User Manual
Page 71
5. Modbus RTU
63
Modbus
5.3. Data and Status Reading (Queries Using Code 03)
5.3.1 Reading Consecutive Multiple Registers
(1) Function
These registers read the contents of registers in a slave.
This function is not supported in broadcast communication.
(2) Start address list
With RC Series controllers, the sizes of send/receive buffers are set to 256 bytes, respectively.
Accordingly, a maximum of 125 registers’ worth of data consisting of 251 bytes (one register uses
two bytes), except 5 bytes (slave address + function code + number of data bytes + error check) of
the above 256 bytes, can be queried in the RTU mode. In other words, all of the data listed below
(total 21 registers) can be queried in a single communication.
It is also available to refer to multiple registers of the addresses in a row at one time of sending
and receiving.
Address [H] Symbol
Name
Sign
Register size
Byte
0500
ALA0
Alarm detail code
1
2
0501
ALA0
Alarm address
1
2
0502
-
Always 0
-
1
2
0503
ALC0
Alarm code
1
2
0504,0505
ALT0
Alarm occurrence time
2
4
8400,8401
TLMC Total moving count
(Note1)
2
4
8402,8403
ODOM Total moving distance
(Note1)
2
4
841A,841B
TIMN
Present time(dedicated for SCON-CA)
2
4
8420,8421
TIMN
Present time
(dedicated for PCON-CA/CFA)
2
4
842E,842F
TFAN Total fan driving time
(dedicated for PCON-CFA)
2
4
9000, 9001
PNOW Current position monitor
{
2
4
9002
ALMC Present alarm code query
1
2
9003
DIPM
Input port query
1
2
9004
DOPM Output port monitor query
1
2
9005
DSS1 Device status query 1
1
2
9006
DSS2 Device status query 2
1
2
9007
DSSE Expansion device status query
1
2
9008, 9009
STAT
System status query
2
4
900A, 900B VNOW Current speed monitor
{
2
4
900C, 900D CNOW Current ampere monitor
{
2
4
900E, 900F
DEVI
Deviation monitor
{
2
4
9010, 9011
STIM
System timer query
2
4
9012
SIPM
Special input port query
1
2
9013
ZONS Zone status query
1
2
9014
POSS Position complete number status query
1
2
9015
SSSE Expansion system status register
1
2
901E
FBFC Force feedback data monitor
{
2
4
Note 1 Dedicated for PCON-CA/CFA, SCON-CA and ERC3