Modbus – IAI America ROBO Cylinder Series User Manual
Page 232

6. Modbus
ASCII
224
Modbus
(4) Sample query
A sample query that reads the current ampere value (address 900C
H
) of a controller of axis No. 0 is
shown below.
Query: 01 03 90 0C 00 02 5E [CR] [LF]
Field
ASCII mode
fixed character string
Converted ASCII
code data [H]
Start
‘:’
3A
Slave address [H]
‘0’, ‘1’
3031
Function code [H]
‘0’, ‘3’
3033
Start address [H]
‘9’, ‘0’, ‘0’, ‘C’
39303043
Number of registers [H]
‘0’, ‘0’, ‘0’, ‘2’
30303032
Error check [H]
‘5’, ‘E’ (In accordance with LRC calculation) 3545
End
‘CR’, ‘LF’
0D0A
The response to the query is as follows.
Response: 01 03 04 00 00 01 C8 2F [CR] [LF]
Field
ASCII mode
fixed character string
Converted ASCII
code data [H]
Start
‘:’
3A
Slave address [H]
‘0’, ‘1’
3031
Function code [H]
‘0’, ‘3’
3033
Number of data bytes [H]
‘0’, ‘4’ (4 bytes = 2 registers)
3034
Data 1 [H]
‘0’, ‘0’, ‘0’, ‘0’
30303030
Data 2 [H]
‘0’, ‘1’, ‘C’, ‘8’
30314338
Error check [H]
‘2’, ‘F’ (In accordance with LRC calculation) 3246
End
‘CR’, ‘LF’
0D0A
The current ampere value is “000001C8” o Convert into decimal number o 456 (mA)
The current ampere monitor value is 456 mA.
Note The data of the response example is simply an example and will vary depending on
various conditions.