Part 3 Positioner Mode

Chapter 6 DS-S-C Compatible Mode

338

Part 3 Positioner Mode

Chapter 6 DS-S-C1 Compatible Mode

In this mode, the same I/O assignments used by the conventional controller model DS-S-C1 are used.

As added functions, the cancellation (CANC) input, interpolation setting input, system battery error output,

and absolute battery error output are available, and the number of positions has been increased.

1. I/O Interface List

Pin

No. Category

Port

No.

Signal name

Signal

symbol

Function overview

Cable

color

1A

P24

External power supply 24 V

P24

1-Brown

1B

016 Position No. 1000 input

PC1000

(Same as PC1 through 800)

1-Red

2A

017

-

1-Orange

2B

018

-

1-Yellow

3A

019

-

1-Green

3B

020

-

1-Blue

4A

021

-

1-Purple

4B

022

-

1-Gray

5A

023 CPU reset

CPRES

The CPU will be restarted at the leading edge of this signal.

1-White

5B

000 Start

CSTR

The actuator will start moving at the leading edge of this

signal.

1-Black

6A

001 Pause

STP

The actuator can be moved when this signal is ON, and will

decelerate to a stop when the signal turns OFF.

2-Brown

6B

002 Cancellation

CANC

The remaining travel distance will be cancelled if this signal

turns ON.

2-Red

7A

003 Interpolation setting

LINE

With the 2-axis specification, linear interpolation operation

will start when the start input signal is turned ON while this

signal is ON.

2-Orange

7B

004 Position No. 1 input

PC1

2-Yellow

8A

005 Position No. 2 input

PC2

2-Green

8B

006 Position No. 4 input

PC4

2-Blue

9A

007 Position No. 8 input

PC8

2-Purple

9B

008 Position No. 10 input

PC10

2-Gray

10A

009 Position No. 20 input

PC20

2-White

10B

010 Position No. 40 input

PC40

2-Black

11A

011 Position No. 80 input

PC80

3-Brown

11B

012 Position No. 100 input

PC100

3-Red

12A

013 Position No. 200 input

PC200

3-Orange

12B

014 Position No. 400 input

PC400

3-Yellow

13A

Input

015 *Position No. 800 input

PC800

Input the position number corresponding to the position you

want to move the actuator to.

Be sure to specify a position input by no later than 6 msec

before the start input signal turns ON.

Position numbers are input as BCD codes. (PC1 through 8

indicate the one’s place, PC10 through 80 indicate the ten’s

place, PC100 through 800 indicate the hundred’s place, and

PC1000 indicates the thousand’s place.)

3-Green

13B

300 *Alarm

ALM

This signal remains ON if the controller is normal. It will turn

OFF if an alarm occurs.

3-Blue

14A

301 Ready

RDY

This signal will turn ON when the controller becomes ready. 3-Purple

14B

302 Positioning complete

PEND

This signal will turn ON once the actuator has moved to the

target position and entered the positioning band.

3-Gray

15A

303

-

3-White

15B

304

-

3-Black

16A

305

-

4-Brown

16B

306 System battery error

SSER

This signal will turn ON when the voltage of the system-

memory backup battery drops to the voltage-low warning

level.

4-Red

17A

Output

307 Absolute battery error

ABER

This signal will turn ON when the voltage of absolute-data

backup battery drops to the voltage-low warning level.

4-Orange

17B

N

External power supply 0 V

N

4-Yellow

Caution: The power wiring polarities are reversed from those of the PNP specification applicable to the

old DS-S-C1 controller. As shown above, pin Nos. 1A and 17B are connected to 24 V and 0 V,

respectively, even in the PNP specification.