Appendix C: Parameter Summary Numeric Quick Reference (continued)
CP-461 Analog Cal Sel
Analog Calibration Select (CP-461) selects the signal (AI1, AI2) on the auxiliary analog board for calibration.
2 = Analog In 2
1 = Analog In 1 (default)
Minimum Value: 1
Maximum Value: 2
Default Value: 1
Units: Coded
CP-462 Analog Cal Ref
Analog Calibration Reference (CP-462) determines which of the two calibration reference points (see list below) are to be
calibrated.
2 = point B
1 = point A (default)
Minimum Value: 1
Maximum Value: 2
Default Value: 1
Units: Coded
CP-463 Analog Ref Val
Analog Reference Value (CP-463) is the value of measured data for the signal at the specified reference point (Analog
Cal Ref, CP-462). Use a voltmeter for voltage mode operation to measure the voltage on the analog signal selected for
calibration at the specified reference point. Enter the measured value in the Analog Ref Val (CP-463).
Minimum Value: -6.0
Maximum Value: 6
Default Value: 0
Units: Volts
CP-464 AO Bit Set
Analog Out Bit Set (CP-464) sets the output value in bits that are used to calibrate the Auxiliary Analog Board's analog
output. Change (tune) this value until the actual output matches the value that you entered for Analog Ref Val (CP-463),
for the selected point.
Minimum Value: -32768
Maximum Value: 32767
Default Value: 0
Units: Bits
CP-465 AO Direct
Analog Out Direct (CP-465) is the value output (in volts or milliamps) at the Auxiliary Analog Board's analog output
when the AO Parameter (CP-290) is set to a “0”.
Minimum Value: -15.0
Maximum Value: 20
Default Value: 0.0
Units: Volts or Milliamps