CONTREX CX-1200 User Manual
Page 407

C - 61
(Continued)
Appendix C: Parameter Summary Numeric Quick Reference (continued)
CP-400 Rmt Scroll
In Remote Scroll (CP-400), enter the number of the Control Parameter that you want the Remote Scroll Up PLC bit (168) or
the Remote Scroll Dn PLC bit (169) to increment or decrement by 1 least significant digit, at the Rmt Scroll Rate (CP-401).
To disable the function, set Rmt Scroll (CP-400) to “0” .
Minimum Value: 0
Maximum Value: 449
Default Value: 351
Units: Parameter CP
CP-401 Rmt Scroll Rate
Remote Scroll Rate (CP-401) is the number of times per second, that the Control Parameter that you entered in Rmt Scroll
(CP-400) is either incremented or decremented by 1 least significant digit , when the Remote Scroll Up PLC bit (168) or
the Remote Scroll Dn PLC bit (169) is active.
Minimum Value: 1
Maximum Value: 100
Default Value: 10
Units: Increments/Decrements
CP-402 DI 1 Shot
Use the Digital Input 1 Shot (CP-402) to create a one scan pulse (one-shot) as the result of a high-to-low (open-to-
closed) transition on any or all of the PLC dedicated inputs. To generate a 1-scan pulse for an inactive high to an active
low transition, enter a “1” in the bit location of corresponding digital input. In the example below, the “1” has been
entered in Digital Input 9.
Digital Input 8
Digital Input 9
Digital Input 10
Digital Input 11
Digital Input 12
Digital Input 13
Digital Input 14
Digital Input 15
Minimum Value: 00000000
Maximum Value: 11111111
Default Value: 00000000
Units: Coded