CONTREX CX-1200 User Manual
Page 360
![background image](/manuals/334431/360/background.png)
C - 14
(Continued)
Appendix C: Parameter Summary Numeric Quick Reference (continued)
MP-108 PLC Mon 1 Val
PLC Monitor 1 Value (MP-108) displays both the description and the value of the PLC bit that was selected in PLC
Monitor 1 (CP-405). Please note that a description of the PLC bit appears on the display line instead of the parameter
name (PLC Mon 1 Val).
Minimum Value: 0
Maximum Value: 1
Units: Coded
MP-109 PLC Mon 2 Val
PLC Monitor 2 Value (MP-109) displays both the description and the value of the PLC bit that was selected in PLC
Monitor 2 (CP-406). Please note that a description of the PLC bit appears on the display line instead of the parameter
name (PLC Mon 2 Val).
Minimum Value: 0
Maximum Value: 1
Units: Coded
MP-110 PLC 15-8
PLC 15-8 (MP-110) displays the status of PLC bits 15-8 (See graphic and list below). A “1” in any bit indicates that the
input is “active”. The digital inputs are active low.
Digital Input 8
Digital Input 9
Digital Input 10
Digital Input 11
Digital Input 12
Digital Input 13
Digital Input 14
Digital Input 15
Description
Default Function
Digital Input 8
Batch Reset
Digital Input 9
Position Reset
Digital Input 10
Re-Learn
Digital Input 11
Phase Advance
Digital Input 12
Phase Retard
Digital Input 13
Block Select A
Digital Input 14
Sync Disable
Digital Input 15
Open Loop
Minimum Value: 00000000
Maximum Value: 11111111
Units: Coded