CONTREX CX-1200 User Manual
Page 411
C - 65
(Continued)
Appendix C: Parameter Summary Numeric Quick Reference (continued)
CP-417 Tmr4 on Tm
Timer 4 on Tm (CP-417) is the time, in seconds, from Tmr4 Out going active (= 1) until Tmr4 Out going inactive (back to
“0”). When Tmr4 becomes disabled, the on-time is retained so the timing can continue when Tmr4 is re-enabled. The
Tmr4 Rst bit (128) in the PLC must be used to reset the on-time to “0”. If you want Tmr4 on-time to be infinite (“On”
until Tmr4 is reset with Tmr4 Rst = 1), then enter a value of “-1” in Tmr4 on Tm (CP-417).
Minimum Value: -1
Maximum Value: 86400
Default Value: -1
Units: Seconds
CP-420 Cntr1 Trig
When the Cntr1 Cnt (CP-421) is greater than or equal to Counter 1 Trigger (CP-420), then the Cntr1 Out bit (32) in the
PLC is set to “1”. If the count is less than Counter 1 Trigger, then Cntr1 Out bit (32) will be “0”.
Minimum Value: 0
Maximum Value: 10000000
Default Value: 10
Units: Counts
CP-421 Cntr1 Cnt
Counter 1 Count (CP-421) is the current count for “Counter 1”. The CX-1200 automatically increments it one count for
every “0” to “1” transition of the Cntr1 Inc bit (130). Counter 1 Count is the default batch counter. Either use the Scroll
keys or enter a new number to change this value. When the PLC program sets Cntr1 Rst bit (135) to “1”, then the
Cntr1 Cnt (CP-421) resets to “0” .
Minimum Value: 0
Maximum Value: 10000000
Default Value: 0
Units: Counts
CP-422 Cntr2 Trig
When the Cntr2 Cnt (CP-423) is greater than or equal to Counter 2 Trigger (CP-422), then the Cntr2 Out bit (33) in the
PLC is set to “1”. If the count is less than, the Counter 2 Trigger, the Cntr2 Out bit (33) will be “0”.
Minimum Value: 0
Maximum Value: 10000000
Default Value: 10
Units: Counts
CP-423 Cntr2 Cnt
Counter 2 Count (CP-423) is the current count for “Counter 2”. The CX-1200 automatically increments it one count for
every “0” to “1” transition of the Cntr2 Inc bit (131). Either use the Scroll keys or enter a new number to change this
value. When the PLC program sets Cntr2 Rst bit (136) to “1”, then the Cntr2 Cnt (CP-423) resets to “0” .
Minimum Value: 0
Maximum Value: 10000000
Default Value: 0
Units: Counts
CP-424 Cntr3 Trig
When the Cntr3 Cnt (CP-425) is greater than or equal to Counter 3 Trigger (CP-424), then the Cntr3 Out bit (34) in the
PLC is set to “1”. If the count is less than, the Counter 3 Trigger, the Cntr3 Out bit (34) will be “0”.
Minimum Value: 0
Maximum Value: 10000000
Default Value: 10
Units: Counts