CONTREX CX-1200 User Manual
Page 384

C - 38
(Continued)
Appendix C: Parameter Summary Numeric Quick Reference (continued)
Minimum Value: 1
Maximum Value: 3
Default Value: 2
Units: Coded
CP-210 Master SP
Master Setpoint (CP-210) is the speed at which you want your system to operate (while in Run) when the Run Mode
(CP-202) is set to "2” (Master Mode).
Minimum Value: -9999999
Maximum Value: 9999999
Default Value: 0.0
Units: EU/Tm
CP-211 Max SP Mstr
Maximum Setpoint Master (CP-211) is an upper limit to the Master SP (CP-210). It will prevent higher entries in Master
SP (CP-210).
Minimum Value: 0
Maximum Value: 9999999
Default Value: 9999999
Units: EU/Tm
CP-212 Min SP Mstr
Minimum Setpoint Master (CP-212) is a lower limit to the Master SP (CP-210). It will prevent lower entries in Master SP
(CP-210).
Minimum Value: 0
Maximum Value: 9999999
Default Value: 0
Units: EU/Tm
CP-220 Follower SP
Follower Setpoint (CP-220) is the speed at which you want your system to operate (while in Run) when the Run Mode
(CP-202) is set to "3” (Follower Mode).
Minimum Value: 1.000
Maximum Value: 999999
Default Value: 0
Units: Ratio
CP-221 Max SP Fol
Maximum Setpoint Master (CP-221) is an upper limit to the Follower SP (CP-220). It will prevent higher entries in
Follower SP (CP-220).
Minimum Value: 0
Maximum Value: 999999
Default Value: 999999
Units: Ratio
CP-212 Min SP Fol
Minimum Setpoint Follower (CP-222) is a lower limit to the Master SP (CP-210). It will prevent lower entries in Master SP
(CP-210).