CONTREX CX-1200 User Manual
Page 413

C - 67
(Continued)
Appendix C: Parameter Summary Numeric Quick Reference (continued)
CP-431 DN Write Parm 2
Enter the number of a Control Parameter to be written to with the DeviceNet poll command in the I/O Assembly Queue.
Minimum Value: 0
Maximum Value: 667
Default Value: 0
Units: CP
CP-432 DN Write Parm 3
Enter the number of a Control Parameter to be written to with the DeviceNet poll command in the I/O Assembly Queue.
Minimum Value: 0
Maximum Value: 667
Default Value: 0
Units: CP
CP-433 DN Write Parm 4
Enter the number of a Control Parameter to be written to with the DeviceNet poll command in the I/O Assembly Queue.
Minimum Value: 0
Maximum Value: 667
Default Value: 0
Units: CP
CP-434 DN Read Parm 1
Enter the number of a Control Parameter or Monitor Parameter to be read with the DeviceNet poll command in the I/O
Assembly Queue.
Minimum Value: 0
Maximum Value: 667
Default Value: 0
Units: CP or MP
CP-435 DN Read Parm 2
Enter the number of a Control Parameter or Monitor Parameter to be read with the DeviceNet poll command in the I/O
Assembly Queue.
Minimum Value: 0
Maximum Value: 667
Default Value: 0
Units: CP or MP
CP-436 DN Read Parm 3
Enter the number of a Control Parameter or Monitor Parameter to be read with the DeviceNet poll command in the I/O
Assembly Queue.
Minimum Value: 0
Maximum Value: 667
Default Value: 0
Units: CP or MP
CP-437 DN Read Parm 4
Enter the number of a Control Parameter or Monitor Parameter to be read with the DeviceNet poll Command in the I/O
Assembly Queue.
Minimum Value: 0
Maximum Value: 667
Default Value: 0
Units: CP or MP